Acest site foloseste cookie-uri pentru a imbunatati experienta de navigare. Daca folositi website-ul nostru, sunteti de acord cu salvarea de cookie-uri in calculatorul / dispozitivul dumneavoastra. Pentru mai multe optiuni cu privire la cookies, accesati sectiunea setari a browser-ului dumneavoastra.

Introducere » Vane sertar FM&UL » Sistem de monitorizare pozitie inchis-deschis pentru sertar cu tija ascendenta


        

Sistem de monitorizare pozitie inchis-deschis pentru sertar cu tija ascendenta

 

Preţ fără TVA : 0,00 RON
Preţ cu TVA (19 %):
0,00 RON

în coş:
  buc  

UL, cUL and CSFM Listed, FM Approved, NYMEA Accepted, CE
Marked
Dimensions: 6.19"L X 2.25"W X 5.88"H
15,7cm L X 5,7cm W X 14,6cm H
Weight: 2 lbs (0,9 kg)
Enclosure: Cover - Die-Cast
Finish - Red Spatter Enamel
Base - Die Cast Zinc
All parts have corrosion resistant finishes
Cover Tamper: Tamper Resistant Screws
Optional Cover Tamper Switch Available
Contact Ratings:
OSYSU-1: One set of SPDT (Form C)
OSYSU-2: Two sets of SPDT (Form C)
15 Amps at 125/250VAC
2.5 Amps at 30VDC resistive
Environmental Limitations:
-40°F to 140°F (-40°C to 60°C)
NEMA 4 and NEMA 6P Enclosure (IP67)
Indoor or outdoor use (Not for use in hazardous locations. See
Bulletin No. 5400705 OSYS-U-EX for hazardous locations).
Conduit Entrances:
2 knockouts for 1/2" conduit provided
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72

General Information
The OSYSU is used to monitor the open position of an OS&Y
(outside screw and yoke) type gate valve. This device is
available in two models; the OSYSU-1, containing one set
of SPDT (Form C) contacts and the OSYSU-2, containing
two sets of SPDT (Form C) contacts. These switches mount
conveniently to most OS&Y valves ranging in size from 2" to
12" (50mm to 300mm). They will mount on some valves as
small as ½" (12,5mm).
The cover is held in place by two tamper resistant screws that
require a special tool to remove. The tool is furnished with each
device and should be left with the building owner or responsible
party. Replacement or additional cover screws and hex keys are
available. See Ordering Information.
Optional Cover Tamper Switch
A field installable cover tamper switch is available as an option
which may be used to indicate removal of the cover. See
Ordering Information.
Testing
The OSYSU and its associated protective monitoring system
should be inspected and tested in accordance with applicable